Uninterruptible Power Supplies (UPS)

 2

Uninterruptible Power Supplies (UPS)
An uninterruptible power supply (UPS) is a crucial device designed to provide power to computers, servers, server rooms, and data centers during main power failures, electrical surges, or unexpected power outages. Easy to install, UPS systems contain a battery that ensures your computer systems continue to run for a specified period, allowing enough time to save work and safely shut down software. For a comprehensive understanding, refer to our complete guide on uninterruptible power supplies (UPS).
Types of UPS Systems
There are several types of UPS systems available:
1.Online UPS:
1.Converts AC input (utility power) to DC and reconverts it to stable AC using an inverter while constantly charging the batteries.
2.Provides continuous power without any interruption during power outages.
2.Standby UPS:
1.Normally outputs AC input (utility power) directly to connected devices.
2.During power outages or abnormal voltage, it switches to battery power via an inverter.
3.May experience a brief power break of a few milliseconds during the switch.
3.Parallel Processing UPS:
1.Supplies power from AC input (utility power) while a bidirectional inverter connected in parallel corrects voltage and absorbs noise.
2.Combines high efficiency and reliability through an online inverter (parallel) system.
4.Hybrid UPS:
1.Operates in three modes: double conversion, economy, and active filter mode.
2.Automatically selects the optimal power mode based on the power situation and load conditions.
3.Seamlessly shifts between modes without any interruption in output voltage.
4.Double conversion mode is used when power quality is poor, and economy mode is used when power quality is good.
Choosing the Right UPS Device
When selecting a UPS, consider the following factors:
Backup time required
Size of the UPS
Number and type of communication ports
 

Specification : 
Capacity  3KVA / 2700W
Input Voltage  (115~300)VAC ± 5
Input Frequency  40Hz~70Hz
Input Power Factor  ≥0.99 @ 100% 
Output Voltage  220VAC ± 3% 
Output Frequency  50Hz ± 0.25 (battery mode)
Dimensions  460x190x330 (MM)
Charging Voltage  82.1VDC ± 1%
Battery Charging Time  6 hours to 90% Maximum 
Charging Current  1A
Conversion Time  0S
Battery Model  12V/7AH (6 units)
Net Weight  20.75KG 
Output Power Factor  0.8 at 40°C ambient temperature
0.9 at 30°C ambient temperature 
Overload Capacity  105%-150% for 47 seconds to 25 seconds
 150%-200% for 25 seconds to 300 milliseconds
 Above 200% for 20 milliseconds (output power factor 0.8)
LED Indicators  Load size
 Battery capacity
 Mains mode
 Battery mode
 Bypass mode
 Fault indication 
Battery Discharge  A beep every 4 seconds when mains power is lost
 A beep every second when the battery is about to be exhausted 
Operating Environment  Temperature 0°C to 40°C, 
 Humidity 20-90% (non-condensing)

Make Appointment