RadiFan AC Fan Filter Unit FFU
FFU is a type of unit used for filtering laminar air and supplying clean air. FFU can bu used standalone or installed modularly.
FFU is the core when making cleanroom equipment for a given space including clean booth, clean bench and cleanroom assembly.
Specification
needs. External size can be altered to suit various type of GRID. Also, we provide professional solutions in respond to changes of external material case, special power supply, or changes of fan configuration.
Features:
Self-contained FFU design
Specially designed casing that combines a high performance AC fan motor with our HEPA/ULPA filter.
Material of casing
Radifan AC provides 50 to 150 Pa of static pressure under the rated airflow with its unique interior design
Speed control
Comes with alternating 5-step speed controller or variable controller. It can also be connected to our software monitoring system.
Specification :
FFU | 2x2 | 2x4 | 4x4 |
Dimension (mm) | 575x575 | 575x1175 | 1175x1175 |
Height | 250x25 (Air Inlet) |
275x25 (Air Inlet) |
310x25 (Air Inlet) |
Pressure Pa @ 0.45m/s | 190 | 280 | 230 |
Power, W | 70~90 | 130~150 | 228~255 |
Current, A | 0.32~0.41 | 0.59~0.69 | 1.06~1.20 |
Casing Material | Hot dipped Galvanized Plate / SUS / Aluminium | ||
Input Supply Voltage, V | 220V, Single Phase, 50/60Hz | ||
Air Speed, m/s | 0.3~0.5 | ||
Filter | HEPA Filter | ||
Filtration Grade | H13~U16 | ||
External Pressure Pa | 90 | ||
Noise Level, dBA | 49~54 | 52~56 | |
Weight, Kg | 18 | 27 | 41 |
Control | EsiDrive II Controller, 5 speed | ||
Optional | Running light | ||
DOP Inlet | |||
DOP Sampling Channel | |||
Pessure Test Hole | |||
Pressure Different Alarm |
Make Appointment